Points clés pour l'utilisation des convertisseurs de fréquence

The braking unit supplier reminds you that in order to ensure the safe and stable operation of the frequency converter, it is very important to meet the allowable operating environment requirements of the frequency converter. In summary, do not let the operating environment of the frequency converter exceed the allowable temperature, and pay attention to the ventilation performance of the frequency converter cabinet. If the ambient temperature of the frequency converter is too high, it will reduce the electrical insulation and corrode the metal parts. Dehumidification should be considered to prevent condensation of the frequency converter. When using a frequency converter under safe operating conditions, the following points should be mastered:

1. The frequency converter must be reliably grounded to ensure safe operation and effectively suppress electromagnetic interference.

2. Frequency converters are not suitable for conducting voltage withstand tests and insulation resistance tests. When doing it, a 500V insulation resistance meter should be used for measurement, and the number of shake tests should be minimized as much as possible. Before insulation, all external main power and control circuits should be disconnected and the main circuit should be short circuited; The ground insulation should be ensured to be above 5 megohms.

3. When controlling the motor with a frequency converter, it is necessary to ensure that the motor has good ventilation conditions, and external ventilation and cooling measures should be taken if necessary.

4. When using a frequency converter with multiple motors, in addition to ensuring that the total current of the motors is less than the rated current of the frequency converter, it is also necessary to calculate the impact of the starting current of at least one motor to avoid overcurrent tripping of the frequency converter.

5. Capacitor compensation devices should not be connected to the output side of the frequency converter to prevent overcurrent protection tripping and even damage to the frequency converter.

6. The operation and stop of the motor driven by the frequency converter cannot be directly operated using low-voltage circuit breakers or AC contactors. It should be operated through the control terminals of the frequency converter, otherwise it may cause the frequency converter to lose control and cause accidents.

7. Avoid driving motors with variable frequency drives that do not match their capacity. A small motor capacity will affect the effective torque output, while a large capacity will increase the harmonic capacity.

8. When the driven motor has a brake, the frequency converter should operate in a free stop mode, and the action signal of the brake must be issued after the frequency converter sends a stop command.

9. When using a frequency converter to drive explosion-proof motors, due to the lack of explosion-proof performance, the frequency converter should be placed outside of hazardous areas.

10. Lorsqu'un convertisseur de fréquence est utilisé pour entraîner un réducteur, sa plage d'utilisation est limitée par le mode de lubrification des pièces rotatives de l'engrenage. En cas de lubrification à l'huile, aucune restriction ne s'applique à basse vitesse. À haute vitesse (au-delà de la vitesse nominale), l'alimentation en huile peut s'avérer insuffisante ; il convient donc de tenir compte de la vitesse maximale admissible.

11. Il est impératif de lire attentivement le manuel d'utilisation avant d'utiliser le convertisseur de fréquence. L'alimentation principale d'entrée et de sortie du convertisseur ne doit pas être inversée, et les bornes « COM » et « GND » ne doivent pas être interverties. Attention : les filtres RFI ne doivent pas être utilisés sur les réseaux électriques dont le neutre n'est pas mis à la terre (systèmes informatiques, réseaux flottants), sous peine de court-circuit à la terre via le condensateur de filtrage, ce qui peut endommager le convertisseur de fréquence.

12. Lors de la phase d'essai, il convient de le faire fonctionner d'abord à vide, puis avec une charge légère, et enfin avec une charge complète.

13. Pendant le fonctionnement du convertisseur de fréquence, il est possible d'inspecter visuellement les conditions de fonctionnement depuis l'extérieur de l'équipement pour détecter toute anomalie et de vérifier les paramètres de fonctionnement du convertisseur de fréquence via le panneau de commande afin de détecter rapidement les problèmes du convertisseur de fréquence et du moteur.

14. Le convertisseur de fréquence doit être nettoyé et dépoussiéré régulièrement afin de maintenir sa propreté interne et le bon fonctionnement de ses conduits d'air.

15. Gardez l'environnement autour du convertisseur de fréquence propre et sec, et ne placez pas d'objets non liés à proximité du convertisseur de fréquence.

16. Après l'installation et l'entretien du convertisseur de fréquence, vérifiez soigneusement l'absence de vis et de têtes de fils manquantes afin d'éviter que de petits objets métalliques ne tombent dans le convertisseur de fréquence et ne provoquent des courts-circuits internes.